ABB Series 10A3200 Armored Metal Tube Purgemeters


Armored purgemeters for low flows of aggressive fluids and high temperature and pressures applications . Available with alarms and 4-20 ma transmitters (Sizes ¼, ⅜, ½, 1") with NPT threads. Integral needle valve option on ¼" size. Large, interchangeable secondaries (indicators).

Model 10A3220

abb armored purge with valve

ABB Armored Purge
Indicator and Valve

Model 10A3220

abb armored purge with differential controller

ABB armored Purge
Differential Controller

Model10A3225

abb armored purge with vertical connections

ABB Armored Purge
Vertical Connections

Model 10A3225

ABB Fischer & Porter 1" Armored Flow Meter

ABB Armored Purge
1" Stainless Steel Metal Tube

Model KFA5-

External Alarm Contacts Card for ABB Fischer & Porter Armored Flow Meters

ABB External Alarm
Relay Module

10A3220 Armored Purge Meter with Horizontal 1/4" NPT

abb armored purge with valve and horizontal 1/4 NPT connections
  • Suitable for most low flow, high pressure and corrosive applications in municipal and industrial settings. Used for gas analyzer systems, various sampling systems, and situations where glass meter tubes are not appropriate for safety reasons.
  • Measures from .05 to 26 GPH; .17 to 115 SCFH
  • Optional Minimum and or Maximum Alarms
  • Optional 4-20 ma transmitter
  • Max Pressure: 580 psig
  • Temperature Limits:

    Viton: 300 °F
    Buna-N: 248 °F
    Kalrez: 285 °F

  • Accuracy: ±6% Full Scale
  • Reproducibility:  ±0.5% F.S.

Armored Purge Meter with Differential Pressure Regulator 1/4"

ABB Fischer & Porter Armored Purge Meter with Flow Controller
  • The Constant Differential Pressure Regulator maintains a constant flow with varying line pressures. It is available in stainless steel and viton with buna-n as an option
  • Measures from .03 to 26 GPH; 0.17 to 115 SCFH
  • Optional Minimum and or Maximum Alarms
  • Optional 4-20 ma transmitter
  • Max Pressure: 200 psig
  • Temperature:

    Viton: 300 °F
    Buna-N: 248 °F
    Kalrez: 285 °F

  • Accuracy: ±6% Full Scale
  • Reproducibility:  ±0.5% F.S.

10A32 Armored Purge Meter with Vertical Connections

ABB Fischer & Porter Armored Purge Meter for Vertical Mounting
  • Suitable for most low flow, high pressure and corrosive applications in municipal and industrial settings. Used for gas analyzer systems, various sampling systems, and situations where glass meter tubes are not appropriate for safety reasons.
  • Measures from 0.26 to 210 GPH; 11.5 to 880 SCFH
  • Optional Minimum and or Maximum Alarms
  • Optional 4-20 ma transmitter
  • Max Pressure: 1450 psig
  • Temperature:

    Viton: 300 °F
    Buna-N: 248 °F
    Kalrez: 285 °F

  • Accuracy: ±6% Full Scale
  • Reproducibility:  ±0.5% F.S.

10A3255 Armored Purge Meter with Vertical Connections

ABB Fischer & Porter 1" Armored Flow Meter
  • Suitable for most low flow, high pressure and corrosive applications in municipal and industrial settings. Used for gas analyzer systems, various sampling systems, and situations where glass meter tubes are not appropriate for safety reasons.
  • Measures from .35 to 13.3 GPM; 1.47 to 55 SCFM
  • Optional Minimum and or Maximum Alarms
  • Optional 4-20 ma transmitter
  • Max Pressure: 1450 psig
  • Temperature:

    Viton: 300 °F
    Buna-N: 248 °F
    Kalrez: 285 °F

  • Accuracy: ±6% Full Scale
  • Reproducibility:  ±0.5% F.S.

External Module for Relay Alarms

External Alarm Contacts Card for ABB Fischer & Porter Armored Flow Meters
CHANNEL TYPE SUPPLY MODEL PART NUMBER
1 SPDT 115 VAC KFA5-SR2-Ex1.W P/N163A012U01
1 SPDT 220 VAC KFA6-SR2-Ex1.W P/N 163A012U05
1 DPDT 115 VAC KFA5-SR2-Ex1. W. LB P/N 163A012U03
1 DPDT 220 VAC KFA6-SR2-Ex1. W. LB P/N 163A012U04
2 SPDT 115 VAC KFA5-SR2-Ex2.W P/N 163A012U02
2 SPDT 220 VAC KFA6-SR2-Ex2.W P/N 163A012U06
1 SPDT 24 VDC KFD2-SR2-Ex1.W P/N D163A011U03
2 SPDT 24 VDC KFD2-SR2-Ex2.W P/N D163A011U06
1 DPDT 24 VDC KFD2-SR2-Ex1.W.LB P/N 163A012U07
Supply Voltage:
120V ac ±15%, 45-65 Hz
Contact Rating:
Max. 250V; Max. 2A
Sensor Switch Cable:
Standard - 6.5 feet
Optional - up to 980 feet
Safety Classification:
The sensor(s) is intrinsically safe for Class I, Div. 1, Group A, B, C & D and Class II, Div. 1, Group E, F & G when connected with control amplifier mounted in non-hazardous location.